Panel Protector / Hardwire / PTS 240 3D H / 2nd
Edition
PE
Down load Specification.
240 Three Phase Delta Surge suppressor
Specifications - Operating:
Maximum Operating Voltage: 240 Volts AC
Typical Leakage Current: <5µ amps
Operation Temperature: - 40 to +85°C
Connectors: Hardwired
Lines Protected: L-L, LH-L, L-N, N-G, L-G
Installation Configuration: Parallel
Specifications - Electronic:
Maximum Surge Current (8x20µs):
Maximum Surge Voltage (1.2x50µs): 10,000 Volts
Capacitance: <4,000 pf
Clamping Voltage: 250 Volts RMS
Clamping Response Time: <5 nanoseconds
Current: Non-Load Bearing
Voltage: Voltage Sensitive
Design: Thermally Fused Hybrid
Operation Indicators: Light Emitting Diode (LED)
Power Dissipation (8x20µs): 51,000,000 Volt Amps
Energy Dissipation: 3800 Joules
UL 1449: 1449 Second Edition
UL Recognized Component: File E121637
USL and CNL Approved: United States / Canada
Dimensions:
Depth 2.500"
Width 4.75"
Length 5.800" (including tabs)
Weight: Approximately 2 lbs.
Pass Voltage Tested to ANSI/IEEE B3 Impulse: UL’s Best 330 V Peak Rating
E-Clips surge suppressors have a . Please see warranty statement for complete product warranty information.